Kidde Airsense Air Heat Box 9-30422The Stratos range of High Sensitivity Aspirating Smoke Detectors are suitable for installation within an area only if the ambient temperature is expected to be above 0C the minimum operating temperature of a Stratos detector is typically -10C check the specification of the particular detector in question. Where the air temperature in the protected area is consistently below this temperature it is imperative that the detector is mounted outside the protected area in an environment where the temperature meets that specified for the detector.However the sampled air from the protected area must be conditioned before it is passed into the detector. The Air Heater Box is designed to raise the temperature of the air drawn from a very cold environment by passing it across a heating element before it passes into the detector. In this manner the problem of condensation on sampling pipework external to the protected area is minimised. Warming the air sample will also ensure the components of the detector operate within the specified temperature tolerances and it reduces the possibility of surface condensation.